ㆍ▷ 24 V, 32 채널(소싱 입력), 7 μs C 시리즈 디지털 모듈
ㆍ▷ DSUB connectivity
ㆍ▷ 60 VDC, CAT I, channel-to-earth isolation
Features
• DSUB connectivity
• 60 VDC, CAT I, channel-to-earth isolation
Specification & Introduction
Input Characterstics
• Number of channels
32 digital input channels
• Input type
Sourcing
• Digital logic levels
OFF state
Input voltage1
≥ (Vsup - 5 V)
Input current
≤150 μA from DI pin
ON state
Input voltage1
≤ (Vsup - 10 V)
Input current
≥330 μA from DI pin
Hysteresis
Input voltage
1.9 V minimum
Input current
65 μA minimum
• Input impedance
30 kΩ ±5%
• I/O protection (Vsup-to-channel)
Input voltage
30 V maximum
Reverse-biased voltage
-30 V maximum
• Hold time2
0 s minimum
• Setup time3
1 μs minimum
• Update/transfer time4
7 μs maximum
• MTBF
955,723 hours at 25 °C; Bellcore Issue 2,
Method 1, Case 3, Limited Part Stress Method
Power Requirements
• Power consumption from chassis
Active mode
615 mW maximum
Sleep mode5
5 mW maximum
• Thermal dissipation (at 70 °C)
Active mode
1.35 W maximum
Sleep mode
1.16 W maximum
Ordering Information