ㆍ▷ 50 V, 16 채널(싱킹 출력), 50 μs C 시리즈 디지털 모듈
ㆍ▷ DSUB connectivity
ㆍ▷ Source up to 1.2 A per channel for all 16 channels or 5 A for one channel
ㆍ▷ Programmable current limits for customizable system protection
Features
• DSUB connectivity
• Source up to 1.2 A per channel for all 16 channels or 5 A for
one channel
• Programmable current limits for customizable system protection
• 60 VDC, CAT I, channel-to-earth isolation
Specification & Introduction
Output Characteristics
• Number of channels
16 digital output channels
• Output type
Sinking
• Power-on output state
Channels off
• Output voltage (V0)
I0 R0
• External power supply voltage range (Vsup)
0 VDC to 50 VDC
• Continuous output current (I0), per channel
All channels on
1.2 A maximum
Four channels on
2.5 A maximum
One channel on
5 A maximum
• Switched output current (10 kHz), per channel
All channels on
1 A maximum
Four channels on
2 A maximum
One channel on
4 A maximum
• Switched output current (20 kHz), per channel
All channels on
0.75 A maximum
Four channels on
1.67 A maximum
One channel on
3.33 A maximum
• Output impedance (R0)
50 mΩ maximum
• Reversed-voltage protection
None
• Number of current limit settings
2 (Limit A and Limit B)
• Current limit range
0 A to 5.1 A
• Current limit resolution
8-bit, 20 mA per LSB
• Current limit accuracy
130 mA + 3% of setting, maximum
• Overcurrent protection threshold selection per channel
Limit A, Limit B, or No Limit
• Overcurrent shutoff response time
1 µs
• Overcurrent refresh configuration
Enabled or Disabled
• Overcurrent refresh period
20 µs to 2550 µs in 10 µs increments
• Overcurrent refresh period accuracy
±7% maximum
• Propagation delay
250 ns maximum
• MTBF
823,106 hours at 25 °C; Bellcore Issue 6,
Method 1, Case 3, Limited Part Stress Method
Power Requirements
• Power consumption from chassis
Active mode
1 W maximum
Sleep mode
25 μW maximum
• Thermal dissipation (at 70 °C)
Active mode
1.5 W maximum
Sleep mode
25 μW maximum
Ordering Information